Electrical Requirements
GREYWATER OR RAIN SYSTEMS USING 110v (1 PUMP):
Refer to page 36 in the Complete Control User Guide.
110v Power: PCB grounded to separate earth ground. 20 dedicated amps to controller.
12/3 wire bundle from controller to pump in 3/4” conduit.
GREYWATER OR RAIN SYSTEMS USING 220v 1 ph (1 PUMP):
Refer to ReWater® 220 VAC One Pump Relay Junction Box Installation Wiring Diagram (PDF)
220v 1 ph Power: PCB grounded to separate earth ground. 30 dedicated amps to external breaker shut-off inline, then to controller. 10/3 wire bundle from controller to pump in 3/4” conduit.
Autofill unit: 20 dedicated amps.
LOS ANGELES COMPLIANT GREYWATER, AND GREYWATER & RAIN LID COMPLIANCE (2 PUMPS)
Refer to ReWater® 220 VAC Pump Relay Junction Box Installation Wiring Diagram (PDF)
200/208/230v 1 ph Power: PCB grounded to separate earth ground. 30 dedicated amps to external breaker shut-off inline, then to controller. 10/3 wire bundle from controller to pump in 1” conduit.
Autofill unit: 20 dedicated amps.
24v FOR ALL CONTROLLERS:
7/18 wires from filter vessel to controller.
2/18 double shielded wires from float switch in primary tank to controller.
All 24v wires shall be in separate conduits from 110/220v wires.